Section 59.11. Story height  


Latest version.
  • D-H occupancies shall be governed by the story height limitations in the following table:


    Construction
    Type
    Maximum
    Story Height
    Fireresistive3 Stories
    Noncombustible1 Story*
    Protected Heavy Timber1 Story
    Ordinary1 Story
    Wood Frame1 Story

    (b) *An additional story shall be permitted in noncombustible construction when the building is 1-hour rated construction or totally protected by an automatic sprinkler system. The maximum story height may be increased by one story.

    (c) Noncombustible construction shall be considered 1-hour rated construction when bearing walls, columns, beams, other supporting members, ceiling/roof assemblies, floor/ceiling assemblies, stairways, and other openings through floors are of 1-hour rated construction.

    (d) The maximum floor area shall not exceed 50,000 square feet unless the floor area is separated by 2-hour fire walls into individual areas not to exceed 50,000 square feet. The undivided floor area may be increased to 100,000 square feet in buildings protected with a total automatic sprinkler system.