Pennsylvania Code (Last Updated: April 5, 2016) |
Title 34. LABOR AND INDUSTRY |
PART I. Department of Labor and Industry |
Chapter 39. Safety StandardsGeneral |
SubChapter B. ELECTRIC SAFETY |
Section 39.106. Isolating live parts by elevation
Latest version.
-
Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:
Voltage of Conductors Elevation (in feet) 300750 7 7502,500 7 2,5007,500 8 7,50030,000 9 30,00070,000 10 70,000100,000 12 Over 100,000 14
Notation
This section cited in 34 Pa. Code § 39.143 (relating to isolation by elevation); 34 Pa. Code § 39.160 (relating to guarding live parts of switches and automatic cut-outs not installed on switchboards); and 34 Pa. Code § 39.199 (relating to guarding or isolating live parts).