Section 39.106. Isolating live parts by elevation  


Latest version.
  • Current-carrying parts need not be guarded if they are maintained at the following distances above the floors which may be occupied by persons:


    Voltage of ConductorsElevation (in feet)
    300—750 7
    750—2,500 7
    2,500—7,500 8
    7,500—30,000 9
    30,000—70,00010
    70,000—100,00012
    Over 100,00014