Section 27.15. Intensity of illumination  


Latest version.
  • The following table shall be used in determining the illumination levels for various office tasks and locations, the column at right indicating acceptable range of footcandles required:

    TABLE I


    DescriptionAcceptable Range of
    Footcandles on the
    Task
    1. General Offices
    General Office Work56-70
    Accounting, Bookkeeping120-150
    Drafting & Designing120-150
    Private Offices56-70
    2. Conference Rooms1/2-70*
    3. Corridors, Elevators, Escalators, Stairways16-20
    4. Lobbies, Reception Areas10-30
    5. Washrooms24-30





    *More than one lighting system and/or dimming area desirable

    Not less than 1/5 the level of nearby offices

    May be more when planned for transition with daylight or other areas

The provisions of this § 27.15 amended January 27, 1978, 8 Pa.B. 252. Immediately preceding text appears at serial pages (8448) to (8458).