Section 245.613. Monitoring standards  


Latest version.
  • (a) By October 12, 1998, a method of leak detection shall be in use and monitored at least monthly. An automatic sensing device, mechanical device or other appropriate method may be used. This method, at a minimum, shall provide a visual examination of the storage tank system by the owner/operator or designated representative. If releases are detected, they shall be corrected and the provisions of Subchapter D (relating to corrective action process for owners and operators of storage tanks and storage tank facilities and other responsible parties) shall be complied with.

    (b) The owner/operator shall assure that a maintenance and general operations check of the storage tank system is performed at least monthly. Deficiencies noted during the check shall be corrected. The small aboveground storage tank general operations and maintenance checklist provided by the owner/operator shall be used to document the monthly operations and maintenance check. The operations and maintenance check shall include:

    (1) A visual examination of the tank system for deterioration, including, but not limited to, the tank, piping, ancillary equipment, foundation and safety equipment.

    (2) A check of the containment areas for accumulation of water and removal of water as necessary.

    (3) Confirmation that containment drain valves are secured in the closed position when not in use.

    (4) Monitoring of the leak detection system.

    (5) A check of vents for restrictions.

    (6) A check of ancillary equipment for operational malfunctions.

    (7) An investigation of conditions that may be a fire or safety hazard, or pose an environmental hazard.

    (8) Observation for evidence of a release of regulated substance from the tank system.

Notation

Cross References

This section cited in 25 Pa. Code § 245.605 (relating to applicability); 25 Pa. Code § 245.612 (relating to performance and design standards); 25 Pa. Code § 245.614 (relating to requirements for closure); and 25 Pa. Code § 252.3 (relating to scope).